Lenze 8200 motec Montageanleitung Seite 117

0.55 kw ... 2.2 kw
Vorschau ausblenden Andere Handbücher für 8200 motec:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

16.
If necessary, change other
parameters
17.
Go to the
ALL
A Check the fan monitoring
setting under code C0608:
– for 8200 motec 0.25...0.37
kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended)
or C0608 = 2!
Stop!
Function must be
activated during
commissioning!
Otherwise, the
controller may be
destroyed through
overheating!
– for all other controllers:
C0608 = 0 ! (default
setting)
B Select additional functions via
codes, if necessary.
When all settings are complete:
18.
Select the setpoint
19.
Enable the controller
20.
The drive should now be running.
L
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
menu
E.g. via potentiometer at
terminals 7, 8, 9
EDK82MV222 DE/EN/FR 9.0
Commissioning
Vector control
X3
20
28
misc002
T
Terminal X3/28 = HIGH
If the drive does not
start, press  in
addition
NNT