T
Commissioning
The most important codes for commissioning
Code
No.
Name
C0013
Deceleration
time main
uSEr
setpoint
C0014
Operating
mode
C0015
V/f rated
frequency
uSEr
C0016
V
boost
min
uSEr
NOS
Possible settings
Lenze
Selection
5.00 0.00
2
2
V/f characteristic control V ~ f
(Linear characteristic with constant
V
boost)
min
3
V/f characteristic control V ~ f
(Square-law characteristic with
constant V
4
Vector control
5
Sensorless torque control with
speed limitation
Torque setpoint via C0412/6
Speed limitation via setpoint 1
(NSET1-N1), if C0412/1 is
assigned, if not via max.
frequency (C0011)
50.00 7.50
0.00
EDK82MV222 DE/EN/FR 9.0
{0.02
1300.00 Reference: frequency change
s}
2
boost)
min
{0.02
960.00
Hz}
{0.01
40.00
%}
IMPORTANT
C0011 ... 0 Hz
Additional setpoint
C0221
Deceleration times can be
activated via digital
signals
C0103
Commissioning without
motor parameter
identification possible
Benefit of identification
with C0148:
– Improved smooth
running at low speed
– V/f rated frequency
(C0015) and slip
(C0021) are calculated
and stored. They do not
have to be entered
For initial selection enter
the motor data and identify
the motor parameters with
C0148
Otherwise commissioning
is not possible
C0015 is calculated and
stored under C0148 when
the motor parameters are
identified
Settings applies to all
mains voltages permitted
Depending on the controller
Setting applies to all mains
voltages permitted
L