Lenze 8200 motec Montageanleitung Seite 116

0.55 kw ... 2.2 kw
Vorschau ausblenden Andere Handbücher für 8200 motec:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

T
Commissioning
Vector control
15.
Start the motor parameter
identification (C0148)
A Ensure that the controller is
inhibited
B Set C0148 = 1
C Enable the controller
D If the segment  becomes
active after approx. 30 s, inhibit
the controller once again.
NNS
}
X3
20
Press 
X3
20
28
}
X3
20
EDK82MV222 DE/EN/FR 9.0
Only when the motor is
cold!
Terminal X3/28 = LOW
28
misc001
Terminal X3/28 =
HIGH
misc002
The identification
starts:
– The segment 
is off
– The motor
consumes current
and makes a
"high-pitched"
tone.
– The motor does not
rotate!
Terminal X3/28 =
LOW
28
misc001
Identification is
completed.
Calculated and
stored:
– V/f rated frequency
(C0015)
– Slip compensation
(C0021)
– Motor stator
inductance (C0092)
Measured and stored:
– Motor stator
resistance (C0084)
= Total resistance
of motor cable and
motor
L