Do not turn the flow control screw beyond its stops! Due to technical
reasons, a minimum volume flow of approx. 20% is always required.
The blow-off volume flow can be set to a value between 20% and 100%.
Commissioning
The ejector may only be commissioned after it has been installed in the machine/
system for which it is intended.
First-time commissioning
1. Make sure that all electrical and pneumatic connections of the ejector are
correctly connected and are firmly fitted.
2. Enter the required menu settings (basic settings, configuration menu, system
menu, and user menu).
3. Switch on the operating voltage.
4. Switch on the operating pressure.
Recommissioning after a downtime
1. Make sure that all electrical and pneumatic connections of the ejector are
correctly connected and are firmly fitted.
2. Switch on the operating voltage.
3. Switch on the operating pressure.
A typical handling cycle is divided into the three steps of suctioning, blowing off and
idle state. In order to check whether sufficient vacuum has been built up, output 2 is
monitored during suctioning.
ECD-LV-EC-xx-NO
Step
Bit
1
IN1
2
OUT2
3
IN1
4
IN2
5
IN2
6
OUT2
Signal state changes from
inactive to active
Adjusting the software menus
The menu is operated using four buttons. Settings are adjusted using the software
menu. The operating structure is split into settings for the home menu and settings
for the configuration menu. For standard applications, adjusting the ejector's
settings in the home menu will suffice. An advanced configuration menu is available
for applications with special requirements.
When settings are changed, undefined states may occur in the system for
short periods of time (for around 50 ms) under certain circumstances.
Vacuum display
Outside of the menus, the ejector is in display mode and displays the current
vacuum.
If there is overpressure in the vacuum circuit, the display "-FF" appears. This
normally occurs in the "Blow-off" operating state.
If the vacuum value is too high (outside of the measurement range), the display "FFF"
appears.
ECD-LV-EC-xx-NC
State
Bit
Suction
IN1
ON
Vacuum
OUT2
> H2
Suction
IN1
OFF
Blow-off
IN2
ON
Blow-off
IN2
OFF
Vacuum
OUT2
< (H2-h2)
Signal state changes from
active to inactive
Home menu
The home menu can be used to adjust and check all of the settings for the ejector's
standard applications.
Adjusting parameters in the home menu
If the buttons
scrolling quickly through the numbers to be changed.
State
1. To adjust the parameters in the home menu, briefly press button
Suction
2. To select the parameter you wish to change, press the button
ON
3. To confirm the parameter, press the button
4. To change the parameter, press the button
Vacuum
5. To save the selected parameter, press the button
> H2
Adjusting the zero point (calibration)
Suction
1. To adjust the zero point of the built-in sensors, briefly press the button
OFF
2. Press the button
3. Press the button
Blow-off
The vacuum sensor is now calibrated.
ON
Configuration menu
Blow-off
An advanced configuration menu is available for applications with special
OFF
requirements. The operating structure appears as follows:
6/1
See fig.
and
Vacuum
< (H2-h2)
Adjusting the configuration menu
If the buttons
scrolling quickly through the numbers to be changed.
To leave the configuration menu, press button
1. To adjust the parameters in the configuration menu, press the button
2. To select the parameter you wish to change, press the button
3. To confirm the parameter, press the button
4. To change the parameter, press the button
5. To save the selected parameter, press the button
Entering the PIN code
1. To enter the PIN code, press the button
2. Press the button
3. To confirm the menu item, press the button
4. Use the buttons
5. To confirm the entry, press the button
6. Use the buttons
7. To save the PIN code, press the button
[Loc] flashes in the display and the configuration menu disappears.
Running the "Reset to factory settings" function
1. To run the "Reset to factory settings" function, press the button
2. To select the menu item [rES], press the button
3. To reset the ejector to factory settings press the button
After confirmation, the display flashes for three seconds and then automatically
returns to display mode.
or
are pressed for around 3 s, the system starts
.
or
or
until [CAL] appears in the display.
to confirm the value.
6/2
or
are pressed for around 3 s, the system starts
.
or
>3 s.
or
to select the [Pin] menu item.
.
or
to enter the first number in the PIN code.
.
or
to enter the other numbers in the PIN code.
>3 s.
17
Setting the switching points
for the air economizer
function
Setting the switching points
for the signal output
Setting the blow-off time
Zero-point adjustment
.
or
.
.
.
.
>3 s.
or
.
.
.
>3 s.
or
.
>3 s.