Configuration
10.4

Menu functions

10.4.1 Open parameter menu/Base parameters

10.4.2 Setting basic parameters

46
Siemens Building Technologies
Fire Safety & Security Products
Prerequisite:
You are logged in as administrator.
Press the following keys to open the Parameter menu/Base parameters:
Keys
Keep
pressed
Prerequisite:
You have opened the Parameter menu/Base parameters menu. See Section
10.4.1: Open parameter menu/Base parameters.
Basic parameter
Device address
Baud rate S1
Parity S1
Baud rate S2
Parity S2
Signal transmitter
Language
Auto logout
Max. camera number
Max. monitor number
Description
Call menu selection.
The LCD indicates:
Parameter menu
Base parameters
Exit menu selection.
The LCD indicates:
Changed parameters
Cancel
Save
1. Select the desired menu item using the joystick
2. Press F10.
Description
Device address between 0 and 99.
Baud rate for serial port COM /COM1A:
1,200, 2,400, 4,800, 9,600 or 19,200 baud
Parity for serial port COM /COM1A: none or even (odd parity cannot
be set!)
Baud rate for serial port COM2: 2,400, 4,800, 9,600 or 19,200 baud
Parity for serial port COM2:
none or even (odd parity cannot be set!)
Switch signal transmitter on/off. Prerequisite: The signal transmitter
must be switched on using DIP switch SW301-8.
See Section 7.5.2: Configure COM2 as an RS485/TTY interface.
German or English. The language setting is effective immediately.
Time after which the control unit automatically switches to the
LOGOFF status; adjustable between 000 and 200 min (000 = no
Auto logout time).
Definition of the highest (maximum) camera number, adjustable
between 1 and 255.
Definition of the highest (maximum) monitor number, adjustable
between 1 and 255.
03.2009