Herunterladen Inhalt Inhalt Diese Seite drucken

Control Unit Interface Com1A And Com1B - Siemens CKA4820 V2 Benutzerhandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Description of the device
7.3.2

Control unit interface COM1A and COM1B

18
Siemens Building Technologies
Fire Safety & Security Products
The control unit interface has two physical connections COM1A and COM1B, but
only one physical processor interface.
COM1A
COM1A is a standard RS232 interface for data transfer.
Pin No.
1
NC
2
Input
3
Output
4
NC
5
GND
6
NC
7
Output
8
Input
9
NC
Control unit interface RS232 (COM1A), 9-pin Sub-D connector
Tab. 3
COM1B
COM1B is adjustable as a current loop (modified TTY interface) or as an RS485
interface. This current loop is referred to below as "TTY".
The video matrix unit is selected via this connection.
Only one connection can be active.
Pin No.
1
Output
2
Output
3
Input
4
Input
5
Input/output
6
Ground
7
Power supply
8
NC
9
Input/output
Control unit interface TTY/RS485 (COM1B), 9-pin Sub-D connector
Tab. 4
Signal (description)
Not used
RxD
TxD
Not used
Signal ground
Not used
RTS
CTS
Not used
Signal (description)
TTY output I+
TTY output I-
TTY input I+
TTY input I-
RS485 line Tx+
External GND
External V+ (15 V)
Not used
RS485 line Tx-
03.2009