7.3

Connections

7.3.1
12 V DC connection
Siemens Building Technologies
Fire Safety & Security Products
All connections are located at the rear of the device (Fig. 2).
Fig. 2
Control unit (rear view)
1
Power supply: 2-pin plug, 12 V DC connection
See Section 7.3.1: 12 V DC connection.
2
Control unit interface: 9-pin Sub-D plug, RS232.
See Section 7.3.2: Control unit interface.
3
Control unit interface: 9-pin Sub-D plug, TTY.
See Section 7.3.2: Control unit interface
4
Telemetry interface: 9-pin Sub-D socket, TTY/RS485.
See Section 7.3.3: Telemetry interface.
A plug for 12 V DC connection is used for the external supply from a suitable
power supply unit.
Connection of the DC power supply is protected against reverse polarity, and is
made using a two-pin plug. The power supply socket is included among the
accessories. The control unit can be connected using this socket to any power
supply unit with DC 12 V/500 mA.
Make sure that the output power of the power supply unit is below 60 VA and the output current below
5 A.
It is recommended to use the PSU230-12 power supply unit for 12 V DC cameras.
See Section 5: Details for ordering.
Description
+
DC 12 V +10 %, -15 %, stabilized (SELV)
-
Ground
Tab. 2
Pin assignments of the power supply socket
Description of the device