7.3.3

Telemetry interface COM2

7.4

Serial interfaces and switches

Siemens Building Technologies
Fire Safety & Security Products
The telemetry interface consists of a physical connection COM2. COM2 is
adjustable as a TTY or RS485 interface. Cameras, dome cameras, and CDC050x
can be controlled via the telemetry interface.
Pin No.
Signal (description)
1
Output
TTY output I+
2
Output
TTY output I-
3
Input
TTY input I+
4
Input
TTY input I-
5
Input/output
RS485 line Tx+
6
Ground
External GND
7
Power supply
External V+ (15 V)
8
NC
Not used
9
Input/output
RS485 line Tx-
Telemetry interface TTY/RS485 (COM2), 9-pin Sub-D socket
Tab. 5
Interface parameters must be set on the Control Unit for certain functions.
Four DIP switches are used for setting these interface parameters. See Section
7.5: Setting interface parameters.
The individual functions of the DIP switches and the corresponding assignment to
the interfaces are described in the following.
Fig. 3
Assignment of DIP switches to interfaces
Description of the device