Werbung

S5-90U/S5-95U
FB10 AWL
NAME :UHR-STEL
BEZ
:WOTG
E/A/D/B/T/Z: E
BEZ
:TAG
E/A/D/B/T/Z: E
BEZ
:MON
E/A/D/B/T/Z: E
BEZ
:JAHR
E/A/D/B/T/Z: E
BEZ
:STD
E/A/D/B/T/Z: E
BEZ
:AMPM
E/A/D/B/T/Z: E
BEZ
:MIN
E/A/D/B/T/Z: E
BEZ
:SEK
E/A/D/B/T/Z: E
BEZ
:FEHL
E/A/D/B/T/Z: A
BEZ
:MODE
E/A/D/B/T/Z: E
:U
=MODE
:=
M
11.1
:UN
M
20.0
:SPB =M001
:R
M
20.0
:
:A
DB
2
:L
=WOTG
:T
DR
4
:L
=TAG
:T
DL
5
:L
=MON
:T
DR
5
:L
=JAHR
:T
DL
6
:L
=STD
:ON
=AMPM
:ON
=MODE
:SPB =VORM
:L
KH 0080
:OW
VORM :T
DR
6
:L
=MIN
:T
DL
7
:L
=SEK
:T
DR
7
:UN
M
11.2
:S
M
11.2
:L
KT 020.1
:SV
T
10
M001 :U
T
10
:BEB
EWA 4NEB 812 6115-01b
UHR STELLEN
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BI
24H-MODUS = 0, 12H-MODUS = 1
(UHRENMODUS STATUSWORT BIT 1)
MERKER IST RUECKGESETZT, WENN
STELLWERTE BEREITS IN DEN
UHRENDATENBEREICH EINGELE-
SEN WURDEN
UHRENDATENBEREICH
WERT FUER WOCHENTAG ABLEGEN
WERT FUER TAG ABLEGEN
WERT FUER MONAT ABLEGEN
WERT FUER JAHR ABLEGEN
WERT FUER STUNDE ABLEGEN
WENN 12H-MODUS EINGESTELLT IST
UND AMPM-BIT = 1 (NACHMITTAGS),
DANN WIRD ENTSPRECHENDES BIT
IM UHRENDATENBEREICH
GESETZT
WERT FUER MINUTE ABLEGEN
WERT FUER SEKUNDE ABLEGEN
STELLWERTE UEBERNEHMEN
(STATUSWORT IST MW10)
UEBERWACHUNGSZEIT STARTEN
BEB, WENN UEBERWACHUNGSZEIT
NOCH NICHT ABGELAUFEN