6.8.2 Solar operation
Solar operation is configured in the submenu Warming/Solar operation. This is shown in figure 10.
The following parameters can be adjusted:
•
Sensor: Defines whether a solar sensor is present. The solar heating function can only be accessed if
a sensor is present. If a solar sensor is present, its temperature values are displayed on the start screen.
•
Solar: Defines whether the solar heating function (solar pump and collector) should be used for
warming up the water temperature
•
Temperature: Defines the target value for the pool water in solar operation.
•
Time valve: Defines the pause time for converting the solar valve. The filter pump is switched off
for this time.
•
Difference: Defines the minimum required temperature difference between solar and pool water
temperature for activating solar operation.
•
Forced: Defines whether the filter pump should be switched on for solar operation outside of the
switching times.
•
Running time: Defines the minimum running time for solar operation.
•
Speed: Defines the speed at which the filter pump should run during solar operation.
Solar operation
Sensor
Solar
Temperature
Min. temp. collector
The solar sensor / collector sensor (PT1000) must be connected to terminal E5.
The collector pump must be connected to terminal A2 (230V).
A bar valve / magnetic valve can be connected to terminal A17 (potential free switch, max. 3A)
for releasing the collector line. For this purpose, voltage must be applied to the terminal on site.
6.8.3 Sensor calibration
Temperature sensor deviation compensation can be configured in the submenu Warming/Sensor
calibration. The entered value is added to the measured value. If the measured value is too high, a negative
corrective value must be entered. If the measured value is too low, a positive corrective value must
be entered. The difference between the measured value and the actual temperature of the pool water must
be entered as the corrective value.
Available
On
31.0°C
20.0°C
Figure 10: Solar operation
Pool control system Control 1.3 / Operation
Solar operation
10 s
Time valve
6.0 K
Difference
Off
Forced
5 min
Running time
30