Pool control system Control 1.3 / Operation
1
In the field
, you can choose the type of backwash valve. You can choose from a bar valve/6-way valve
and BaduTronic. Please use the 6-way valve setting with an OmniTronic.
2
In the field
, you can adjust the backwashing running time.
The bar valve must be connected to output A6. The OmniTronic must be connected to inputs E1 and E10
and output A6.
6.7.2.4
Clear rinsing settings
The backwashing parameters can be adjusted in the submenu Processing/Filter cleaning/Clear rinsing
settings. This settings menu corresponds to backwashing and is explained under 6.7.2.3.
6.7.2.5
Pause
The pause between the individual filter cleaning steps can be adjusted under Processing/Filter
cleaning/Pause. This is used to switch off the pump during the backwashing steps to facilitate an
unloaded transition. The set pauses (0-200 s) also apply for the steps in an optional clear rinsing cycle.
6.7.2.6
Forced channel
The Forced channel submenu is only available when a channel pool has been set as the pool type
(Processing/Level regulator/Pool type). After backwashing, the filter pump runs for the set time
(max. 200 min), regardless of the switching times, at normal speed again.
23
Backwash setting
Valve type
Backwash duration
Figure 4: Backwashing switching times
Bar valve
1
120 s
2