6.7.8 Lowering valve
The function of the lowering valve cannot be changed in the control system. The lowering valve terminal
is only triggered for channel pools. With skimmer pools, the terminals can be used as freely-programmable
terminals.
The lowering valve is automatically activated as soon as there is an input signal at input E8
(pool cover closed). The lowering valve is supplied with continuous voltage (230V) for the pool cover.
The lower valve is connected at terminal A8.
6.7.9 Forced ON
The forced switch-on for the filter pump can be configured in the submenu Processing/Forced on.
The input for the forced switch-on of the filter pump is defined here. As long is a signal is present at this
input, the filter pump will run at normal speed.
The switch for the forced switch-on must be connected to terminal E11.
6.7.10 Forced OFF
The forced switch-off for the filter pump can be configured in the submenu Processing/Forced on.
The input for the forced switch-on of the filter pump is defined here. As long is a signal is present at this
input, the filter pump will not be provided with power.
The switch for the forced switch-on must be connected to terminal E12.
The delay for the forced switch-on or switch-off can be freely selected between 1-10 seconds.
WARNING!
Make sure that the pool cover does not come into contact with the pool body
when the lowering valve is activated (lower water level in the pool). If there is
contact, there is a risk of material damage while the pool cover is opening!
Pool control system Control 1.3 / Operation
28