63 Alarms and Errors
Fault
LED at the insulation
monitoring device
orange, glowing
LED at the insulation
monitoring device
red, glowing
LED at the insulation
monitoring device
red, flashing
LED at phase monitor-
ing device red, flashing
28
Possible cause
Resistance is below the early
warning limit of
100 kΩ - consumer could
be damaged and should be
checked, Instagrid LINK MAX
continues to work
Resistance is below the
alarm limit of 50 kΩ - output
is switched off for safe-
ty reasons
Internal error of the insula-
tion monitoring device
One or several cables are not
connected to the Insta-
grid LINK MAX
The socket outlet of the
Instagrid ONE is used in-
stead of the Neutrik output
Instagrid ONE is not
Instagrid link MAX-capable
Corrective action
Check the consumer for damage
Insulate and check each connected
device for damaged insulation or cables
Rectify the error and reset the Instagrid
LINK MAX by opening the right hand
fuse box and pressing the "Reset" but-
ton on the insulation monitoring device
Contact the Instagrid After
Sales Service
Check whether each Instagrid ONE is
working correctly and is compatible with
the Instagrid LINK MAX Delete all errors
on the Instagrid ONE devices