Code
Alarm code
Pre-alarm
EVD EVO regulation alarm
201
301
(uPC)
EVD EVO system alarms probe
202
302
errors alarm (uPC)
203
303
Reserved (uPC)
No communication between
204
304
inverter and uPC. (uPC error)
Inverter not compatible with
205
305
the compressor selected (uPC)
Delta P greater than the
206
306
permit at start up (uPC)
207
307
Low pressure limit
Please Note that the pre-alarms are automatic reset, while the alarms are manual rearmament.
The 3.9.0 software version has been introduced to reset the alarms via the ON/OFF remote contact if
enabled. From on position, if it switches to off and returns to on within 5 seconds resets the alarms; The
ON/OFF contact can be performed at maximum 3 reset every hour.
First you have to reset the alarms with "R" key.
In case of power failure the alarms are reset.
Causes
Control wiring
Control wiring
Control wiring
Control wiring
Control wiring
Control wiring
Discharged unit
NOTICE
MODUCONTROL
25/01 6343841_06
Note
75