Index - String MIN value MAX value
0
J Ad1
Index - String MIN value MAX value
0
L 8d1
Index - String MIN value MAX value
0
n A51
Index - String MIN value MAX value
P St1
-25 °C
Index - String MIN value MAX value
o LA1
0 °C
Index - String MIN value MAX value
r St2
-25 °C
Index - String MIN value MAX value
Q LA2
0 °C
60
Modbus supervisor address
This parameter indicates the Modbus address assigned to the supervisor; this ad-
999
dress will be used in the communication between supervisor and Moducontrol.
Supervisor baudrate
This parameter indicates the speed of communication between supervisor and
Moducontrol; this speed is set on the basis of the value selected for this parameter:
2
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
Enabling of supervisor writing
This parameter indicates the speed of communication between supervisor and
Moducontrol; this speed is set on the basis of the value selected for this parameter:
1
0 = write command disabled;
1 = write command enabled;
Remember that the read commands are always active.
Air temperature limit 1
This parameter indicates the external air temperature at which the machine can
45°C
produce its maximum water value (this value is specified in parameter P - St1).
Water temperature limit 1
This parameter indicates the maximum temperature of the water produced, in line
70°C
with the outside air temperature specified in parameter O - LA1.
Air temperature limit 2
This parameter indicates the external air temperature at which the machine can
45°C
produce its maximum water value (this value is specified in parameter R - St2).
Water temperature limit 2
This parameter indicates the maximum temperature of the water produced, in line
70°C
with the outside air temperature specified in parameter Q - LA2.
Parameter function
Parameter function
Parameter function
(*)
Parameter function
(*)
Parameter function
(*)
Parameter function
(*)
Parameter function