Index - String MIN value MAX value
d trA
0
Index - String MIN value MAX value
E bAF
0
Index - String MIN value MAX value
F tbF
0 s
Index - String MIN value MAX value
G ORE
0 °C
Index - String MIN value MAX value
H Ati
40 °C
Index - String MIN value MAX value
0
i SCr
Disabling compressors and supplementary heater
This parameter enables the possibility to join the ID digital clamp (marked on the
electric card enclosed with the unit as TRA) with a room thermostat on which the
functioning of the compressors and supplementary electric heaters will be disabled.
Remember also that setting this parameter with a value of:
- 1 or 2, you ENABLE this function.
- 0 or 3, you DISABLE this function.
3
Remember that the OPEN status of the clamp means:
the function blocks the compressors and electric heaters if the parameter is set at 1
the function blocks the compressors, pump and electric heaters if the parameter is
set at 2
the pump alarm (as in the previous software version), if the parameter is set at 3
Remember also that by setting this parameter at 3, the moducontrol card is compat-
ible with the previous software version (3.6).
Enabling of flow switch by-pass
In those units that produce domestic water, the flow switch alarm can be bypassed
1
to allow the correct synchronisation between a diverting valve installed in the sys-
tem, and unit functioning during the production of hot domestic water.
Time for flow switch bypass
300 s
This parameter allows you to establish the time (in seconds) for flow switch bypass.
High room temperature standby
This parameter lets you establish the room temperature threshold above which the
70 °C
heat pump is disabled; once the threshold has been exceeded, the compressor and
pump are switched off.
High temperature threshold for input water
This parameter indicates the temperature of the input water above which the pump
is switched off and a pre-alarm is generated. After the intervention of the pre-alarm,
80 °C
there is a waiting time of 15 minutes before the pump starts up again. After the
third intervention, the machine goes into alarm/lockout. Active also with the pump
switched off, and the chiller in standby. In the latter case, the alarm is generated.
Screensaver configuration
This parameter indicates the configuration of the screensaver:
- value 0, screensaver disabled;
- value 1, screensaver with visualisation of the dashes (to be used with the control
2
panels with software prior to version 1.3);
- value 2, screensaver without visualisation of the dashes (to be used with the con-
trol panels with software from version 1.3 onwards).
MODUCONTROL
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function