MODUCONTROL
25/01 6343841_06
Index - String MIN value MAX value
0
9 PAN
Index - String MIN value MAX value
A ASA
0
Index - String MIN value MAX value
b ASP
0
Index - String MIN value MAX value
C AA5
0 s
58
Panel control configuration
This setting configures the type of control applicable to the units; depending on the
value decided for this setting, the controls on the functioning mode (HEAT/COOL)
and the unit on/off command will be managed in the following way:
Set value 0:
- Setting functioning mode = set parameter 0
- ON/OFF control = from the panel on the machine
Set value 1:
3
- Setting functioning mode = set parameter 0
- ON/OFF control = from the remote panel
Set value 2:
- Setting functioning mode = set from remote contact
- ON/OFF control = from the panel on the machine
Set value 3:
- Setting functioning mode = set from remote contact
- ON/OFF control = from the panel on the machine
Enabling DHW
In the heat pump models, there is the possibility to produce hot water for domestic
use; this production has its own modifiable setting and its own band (parameters
E, F user menu); with this parameter you can make parameters E and F visible and
usable. Remember that to guide the domestic water production request, once the
function has been activated you must use digital input ID6 (marked on the electric
card enclosed with the unit as TWS). Remember also that setting this parameter
with a value of:
- 1, you ENABLE the domestic water function.
1
- 0, you DISABLE the domestic water function.
The CLOSED status of the clamp means the domestic water function is ACTIVE. This
function is available from software version 3.7 (the software version is visible as a
reading, with index E). The minimum compressor functioning time, and the defrost-
ing time, take priority over the production of domestic water. From software version
4.2, when domestic water is activated the adjustment is automatically set on the
basis of the output temperature, regardless of the value of the parameter (0) in this
menu.
Power dedicated to domestic water production
In those units that can produce domestic water, once this function has been activat-
ed it is possible to decide the percentage of power to use for the production. This
1
function allows you to set a threshold to guarantee reduced energy consumption
during domestic water production.
Standby time in Input/Output
This parameter allows you to establish the standby time (in seconds) for reversing
600 s
the 3-way valve inserted in the system for producing domestic water.
Parameter function
Parameter function
Parameter function
Parameter function