AERMEC MODUCONTROL Bedienungsanleitung Seite 63

Elektronische regelung
Vorschau ausblenden Andere Handbücher für MODUCONTROL:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Index - String MIN value MAX value
0
1
Index - String MIN value MAX value
-20 °C
2
Index - String MIN value MAX value
0
3
Configuration of the heating cable (ANK only)
Setting the output to which the heating cable is connected:
0- no heating cable
1- heating cable on the CPA output (the parameter (0) of the menu with pass-
2
word=72 "according to CP must be 0")
2- heating cable on the VGC output if not used (the configuration of the dip switches
must be: DIP1 = ON, DIP2=ON, DIP5=ON, DIP8=OFF, DIP9=OFF)
Heating cable setpoint (ANK only)
Heating cable activated with an external air temperature lower than the value of
10 °C
this parameter. Heating cable deactivated with an external air temperature higher
than the value of this parameter, plus 1.0° hysteresis.
Thermostat pump switch-off
0 = the pump continues to function when the set point temperature is reached.
1 = the pump switches off when the set point temperature is reached (when this op-
1
tion is selected, the adjustment is automatically activated on the basis of the input
temperature). This parameter is only visible with the adjustment on the basis of the
input temperature (parameter (0) =1 or 2).
MODUCONTROL
Parameter function
Parameter function
Parameter function
25/01 6343841_06
63