Cooling mode
SF1
SF2
Heating mode range
SC1
SC2
Index - String MIN value MAX value
-20 °C
6 SF1
Index - String MIN value MAX value
-40 °C
7 tF1
Index - String MIN value MAX value
-20 °C
8 SF2
Index - String MIN value MAX value
-40 °C
9 tF2
TF1
TF2
TC1
TC2
Setting cooling temperature setpoint 1
This parameter indicates the maximum value of the cooling setting, corresponding
26 °C
with the minimum outside air temperature (index (7) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
Setting the outside air temperature 1
This parameter indicates the minimum outside air temperature taken into consider-
50 °C
ation for cooling compensation. This parameter is only visible if the compensation
function has been activated (index (5) user menu).
Setting cooling temperature setpoint 2
This parameter indicates the minimum value of the cooling setting, corresponding
26 °C
with the maximum outside air temperature (index (9) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
Setting the outside air temperature 2
This parameter indicates the maximum outside air temperature taken into consid-
50 °C
eration for cooling compensation. This parameter is only visible if the compensation
function has been activated (index (5) user menu).
MODUCONTROL
SF1: index (6) user menu;
SF2: index (8) user menu;
TF1: index (7) user menu;
TF2: index (9) user menu;
SC1: index (A) user menu;
SC2: index (C) user menu;
TC1: index (B) user menu;
TC2: index (d) user menu;
Parameter function
Parameter function
Parameter function
Parameter function
25/01 6343841_06