5.4 Notes on the mains supply connection of the product
NOTE
Mains supply connection
On site, ensure the correct pre-fusing and the correct cable cross-section
of the mains supply connection cable.
Rated current: See name plate/data sheet
Rated current
35-45 A
45-55 A
55-70 A
70-85 A
Selection of the mains supply connection cable
Rated
Mains supply
current
connection cable
35-45 A
5 x 16 mm²
45-55 A
4 x 25 mm²
Tab. 63: Selection of the mains supply connection cable
NOTE
Rated current: See name plate/data sheet.
Dimensioning: Mains supply connection cable up to a maximum cable
length of 50 metres.
ATTENTION
When connecting the CEE connection plug to the on-site mains
connection, ensure that the field rotates clockwise!
15028844-00
Back-up fuse
Circuit breaker 3x50 A category C
Circuit breaker 3x63 A category C
Circuit breaker 3x80 A category C
Circuit breaker 3x100 A category C
Tab. 62: Selecting the pre-fusing
Rated
current
55-70 A
70-85 A
- 135 -
Mains supply
connection cable
4 x 35 mm²
4 x 50 mm²
EN