Ring Coupling
Parameter Value
single
P-2
dual-master-inband
dual-master-outband Configure the operating mode of the ring
dual-slave-inband
dual-slave-outband
slot no./port no.
P-3
slot no./port no.
P-4
ring-only
P-5
network
normal
P-6
extended
RM CLI HiOS-2A GRS1040
Release 6.1 09/2016
Meaning
Configure the operating mode of the ring
coupling to single. Both of the coupling
ports are local to the switch, switch per-
forms master and slave functions.
Configure the operating mode of the ring
coupling to dual-master-inband. The second
coupling port is on a remote switch, local
switch is master, communication over net-
work.
coupling to dual-master-outband. The second
coupling port is on a remote switch, local
switch is master, communication over dedica-
ted control port.
Configure the operating mode of the ring
coupling to dual-slave-inband. The second
coupling port is on a remote switch, local
switch is slave, communication over network.
Configure the operating mode of the ring
coupling to dual-slave-outband. The second
coupling port is on a remote switch, local
switch is slave, communication over dedica-
ted control port.
Select the ring coupling mode for a ring net-
work. Both of the network segments that are
coupled are HIPER rings.
Select the ring coupling mode for a bus or
mesh network. The network segment adjacent
to the switches that handle the ring cou-
pling is not a HIPER ring.
Select the ring coupling mode for normal
redundancy mode. The slave does not respond
to a failure in the remote ring or network.
Select the ring coupling mode for extended
redundancy mode The slave responds to a fai-
lure in the remote ring or network.
43.1 ring-coupling