alpha innotec EasyPACK ECO Nias THAEQI 270-10 Bedienungsanleitung Seite 54

Wärmepumpen mit lueftgekuehlter verfluessigung und axialventilatoren

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

• alarm code and description
• management of alarms log.
o In particular, for every alarm, the following are memorised:
• date and time of intervention;
• in/out water temperature values as soon as the alarm was triggered;
• the evaporation and condensation pressure values at the time of the alarm;
• alarm delay from when the connected device is switched on;
• compressor status at the time of the alarm;
o Advanced functions:
• Pump Energy-Saving management;
• evaporator pump control KPE, contactor recovery pump command KPR and KPDS desuperheater Pump Control in the case of external supply of electric
pumps (to be installed by the installer). For the unit to operate properly, activation of the recovery pump, by the installer, must be controlled by means of a
specific discrete output provided in the board on the unit;
• High-Pressure Prevent function with forced cooling capacity partialisation for a high outdoor temperature (in summer mode);
• the EEO - Energy Efficiency Optimizer function allows unit efficiency to be optimised by acting on the electrical absorption, thereby minimising consump-
tion. The algorithm identifies the optimal point that minimises the total absorbed power (compressors+fans) of the unit by actuating the fan rotation speed.
The function allows for an increase in seasonal efficiency of up to 4% if the unit is equipped with the FIEC condensing control accessory with EC fans.
• VPF_R control: (Variable Primary Flow in the main exchanger). VPF_R includes the temperature probs, the inverter management and the management
software of the chiller;
• set-up for serial connection (SS/KRS485, FTT10/KFTT10, BE/KBE, BM/KBM, KUSB accessory);
• possibility to have a digital input for remote management of double set point (DSP);
• possibility of having a digital input for the production of domestic hot water by means of a 3-way diverter valve (CACS contact). In this case, there is the
possibility of using a temperature probe instead of the discrete input. (refer to the specific section for more details);
• option of having domestic hot water diverter valve (VACS) control;
• possibility to have an analogue input for the shifting Set-point (CS) via a 4-20mA remote signal;
• management of time bands and operation parameters with the possibility of daily/weekly functioning programs;
• check-up and monitoring of scheduled maintenance status;
• computer-assisted unit testing;
• self-diagnosis with continuous monitoring of the unit functioning status.
• MASTER/SLAVE management logic integrated in single systems (SIR - Sequenziatore Integrato - Integrated Sequencer) -Refer to the specific section for
more details
o Set-point regulation via the AdaptiveFunction Plus with two options:
• fixed set-point (Precision option);
• set-point sliding (Economy option).
2.2. ACCESSORIES
Factory Fitted Accessories
P1
Installation with pump
P2
Installation with increased static pressure pump
DP1
Installation with double pump, including an automatically activated pump in stand-by
DP2
Installation with increased static pressure double pump, including an automatically activated pump in stand-by
CAC
Compressor aphonic ear muffs
RM
Cooling circuit outlet valves
Modulating condensing control with fans with EC motor (Brushless) as standard in sizes 270÷285 – 10-11
FIEC
SFS
Soft Starter compressors
Power factor correction capacitors (cosφ>0.94)
CR
FDL
Forced Download Compressors. Compressor switch-off to limit the absorbed current and power (digital input)
GM
Refrigerant circuit high and low pressure gauges
RQE
Electrical panel resistance (recommended for low outdoor air temperature)
Evaporator antifreeze resistor to prevent the risk of ice formation inside the exchanger when the machine is switched off (as long as the
RA
unit is not disconnected from the power supply)
27W electric pump antifreeze heater (available with P1-P2-PR1-PR2 set ups); this is used as protection against ice forming in the heat
RAE1
exchanger when the machine is switched off (as long as the unit is electrically powered)
27W antifreeze electric heater for double motor-driven pumps (available for DP1-DP2-DPR1-DPR2 installations); to prevent the water
RAE2
contained in the pump from freezing when the machine is switched off (as long as the unit is not disconnected from the power supply)
H5xxxxx
54
EasyPACK ECO - Nias
Pac
Compressor consumed power
Pav
Fan consumed power
Pt
Total absorbed power
Pa
Absorbed power
Hp
Condensation pressure
54