2.12. MAINTENANCE
IMPORTANT!
Maintenance is reserved exclusively for skilled personnel from workshops authorised, qualified to operate on this type of products. Pay close atten-
tion to the danger signs on the unit. Use the personal protective equipment foreseen by current laws. Pay the utmost attention to the symbols lo-
cated on the unit. Use EXCLUSIVELY original spare parts.
IMPORTANT!
Always use the personal protective equipment foreseen by law (goggles, earmuffs, gloves, etc.).
DANGER!
Always use the general circuit breaker protecting the entire system before carrying out any maintenance work on the unit, even if it is for inspection
purposes only. Lock the general circuit breaker in the zero position to make sure that no one accidentally powers the machine.
DANGER!
Pay attention to high temperatures near the compressor heads and the flow pipes of the cooling circuit.
Control
General cleaning and inspection of the
unit
Finned coils
Fans
Compressor: oil check
Exchangers
Water filter
IMPORTANT!
Provide mandatory controls and inspections pursuant to EU 517/2014.
General cleaning and inspection of the unit
Every six months, the unit should be cleaned using a moist cloth. The general conditions of the unit should always be checked every six months. Any corro-
sion must be treated with protective paints in order to prevent possible damage.
Cleaning of Finned Coils
DANGER!
Pay attention to the lugs and edges of the battery.
The coils must be washed and brushed gently with water and soap. Remove any foreign bodies from the condensing coils which may block the passage of
air, such as: leaves, paper, debris, and so on; Replace the coils should it not be possible to clean them. Failure to clean the coils increases pressure drops
and therefore reduces overall machine performance. For better battery protection, it is recommended to install the RPE accessories (battery protection
networks) or FMB (metal filters batteries).
H5xxxxx
75
Frequency
Every 6 months, the unit must undergo general
washing and its status must be checked
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
Every 6 months
At least every 12 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
EasyPACK ECO - Nias
Notes
Any points where corrosion is starting need to be touched up
with protective paint.
The coils must be kept clear from any obstructions. If needed,
they must be washed with detergents and water. Brush the fins
gently to keep them from being damaged.
The fan grilles must be kept clear from any obstructions. Make
sure the motors and fan blades are clean and that there are no
abnormal vibrations.
The units are equipped with oil sight glasses on the compressor.
The lubricating oil level in the compressor can be checked by
means of the sight-glass.
Any incrustation of the exchanger may be detected by measuring
the pressure-drop between the inlet and outlet pipes, using a dif-
ferential pressure gauge.
It is mandatory to install a mesh filter on the unit's inlet water pip-
ing. This filter must be cleaned from time to time.