MIXING HEATING CIRCUIT > S2.x
Parameter
Parameter description
AMPLIFICATION OF ROOM TEMPERATURE
S2.1
DEVIATION FOR MIXING HEATING CIRCUIT
PARALLEL SHIFT OF THE HEATING CURVE FOR
S2.2
MIXING HEATING CIRCUIT
BOOST HEATING DURATION BY NIGHT/DAY
S2.3
TEMPERATURE SWITCHOVER MIXING CIRCUIT
REQUIRED ROOM TEMPERATURE INCREASE BY
S2.4
BOOST HEATING FOR MIXING CIRCUIT
CIRCULATION PUMP UWP OPERATION MODE
S2.5
0 - circulation pump for mixing heating circuit (standard),
1 - pump UWP switches OFF, when time program P1=OFF,
2 - pump UWP switches OFF, when time program P2=OFF,
3 - pump UWP switches OFF, when the selected time program is OFF.
MINIMAL STAND- PIPE TEMPERATURE FOR
S2.6
MIXING CIRCUIT
MAXIMUM TEMPERATURE OF STAND- PIPE
S2.7
MIXING CIRCUIT
MIXING VALVE - DEAD ZONE REGULATION
S2.8
AMPLIFICATION OF 3-POINT REGULATION
S2.9
FOR THE MIXING VALVE
INTEGRATION CONSTANT FOR 3-POINT
S2.10
REGULATION OF THE MIXING VALVE
DIFFERENTIAL CONSTANT
S2.11
MAXIMUM FLOOR TEMPERATURE
S2.12
MINIMUM STAND-PIPE TEMPERATURE
S2.13
FOR COOLING
Service settings manual
Setting span
0,0 ÷ 3,0
-15 ÷ 15
0 ÷ 200
0 ÷ 8
0 ÷ 3
10 ÷ 90
20 ÷ 150
1,0 ÷ 3,0
0,5 ÷ 2,0
0,4 ÷ 2,5
0,4 ÷ 2,5
10 ÷ 70
10 ÷ 20
42
Units Default
setting
-
1,0
K
0
min
0
K
4
-
0
°C
20
°C
85/45
K
1
-
1
-
1
-
1
°C
25
°C
15