Herunterladen Inhalt Inhalt Diese Seite drucken

Reset And Factory Settings; General System Reset; Factory Settings; Restoring The Factory Settings - DAB ESYBOX MAX 60/120M Installations- Und Wartungsanleitungen

Vorschau ausblenden Andere Handbücher für ESYBOX MAX 60/120M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 124
After resetting the factory values the password is set back at "0". Each change of the password takes effect when Mode or Set is pressed and
each subsequent change of a parameter implies typing in the new password again (e.g. the installer makes all the settings with the default PW
value = 0 and lastly sets the PW so as to be sure that the machine is already protected without any further action).
If the password is lost there are 2 possibilities for editing the parameters of the device:
Make a note of the values of all the parameters, reset the device with the factory values, see paragraph 9.3.
The reset operation cancels all the parameters of the device, including the password.
Make a note of the number present on the password page, send a mail with this number to your service centre, in a few days you will
be sent the password to unlock the device.
8.6.20.1 Password for multipump systems
When the PW is typed in to unlock a device in a set, all the devices are unlocked.
When the PW is changed on a device in a set, all the devices receive the change.
When activating protection with a PW on a device in a set (^ and ˅ on page PW when PW≠0), the protection is activated on all the devices (to
make any change you are asked for the PW).

9. RESET AND FACTORY SETTINGS

9.1 General system reset

To reset the system, press and hold the 4 keys simultaneously for 2 seconds. This operation is the same as disconnecting the power, waiting for
it to close down completely and supplying power again. The reset does not delete the settings saved by the user.

9.2 Factory settings

The device leaves the factory with a series of preset parameters which may be changed according to the user's requirements.
Each change of the settings is automatically saved in the memory and, if desired, it is always possible to restore the factory conditions (see
Restoring the factory settings par 9.3 - Restoring the factory settings).

9.3 Restoring the factory settings

To restore the factory values, switch off the device, wait until the display has switched off completely, press and hold down the "SET" and "^"
keys and turn on the power; release the two keys only when the letters "EE" appear.
Once all the parameters have been set, the device returns to normal operation.
NOTE: Once the factory values have been restored it will be necessary to reset all the parameters that characterise the system (gains, setpoint
pressure, etc.) as at the first installation.
Identifying code
TK
LA
SP
P1
P2
P3
P4
RI
OD
RP
AD
PR
MS
EK
Description
Backlight lighting T.
Language
Setpoint pressure [bar]
Setpoint P1 [bar]
Setpoint P2 [bar]
Setpoint P3 [bar]
Setpoint P4 [bar]
Revs per minute in manual
mode [rpm]
Type of plant
Pressure decrease to restart
[bar]
Address configuration
Remote pressure sensor
Measuring system
Low pressure function on suction
ENGLISH
Value
2 min
ENG
3,0
2,0
2,5
3,5
4,0
3000
1 (Rigid)
0,3
0 (Auto)
Disabled
0 (International)
0
(disabled)
67
Installation Memo

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Esybox max 60/120tEsybox max 85/120t

Inhaltsverzeichnis