Active with low signal on
8
Active with high signal on
9
8.6.15
Setup of the outputs OUT1, OUT2
This section shows the functions and possible configurations of outputs OUT1 and OUT2 of the I/O control unit, with wireless connection to the
device, set by means of parameters O1 and O2.
For the electrical connections, refer to the control unit manual.
The factory configurations can be seen in Table 16.
8.6.16
O1: Setting output 1 function
Output 1 communicates an active alarm (it indicates that a system block has occurred). The output allows the use of a normally open clean
contact.
The values and functions indicated in Table 17 are associated with the parameter O1.
8.6.17
O2: Setting output 2 function
Output 2 communicates the motor running status. The output allows the use of a normally open clean contact.
The values and functions indicated in Table 17 are associated with the parameter O2.
Output
configuration
0
1
2
3
8.6.18
RF: Fault and warning reset
Holding down the ^ and ˅ keys together for at least 2 seconds deletes the history of faults and warnings. The number of faults present in the
log is indicated under the symbol RF (max 8). The log can be viewed from the MONITOR menu on page FF.
8.6.19
PW: Change password
The device has a password-enabled protection system. If a password is set, the parameters of the device will be accessible and visible but it will
not be possible to change them.
When the password (PW) is "0" all the parameters are unlocked and can be edited.
When a password is used (value of PW different from 0) all modifications are blocked and "XXXX" is displayed on the page PW.
If the password is set it allows to navigate through all the pages, but at any attempt to edit a parameter a pop-up appears, asking you to type in
the password. When the correct password is typed in the parameters are unlocked and can be edited for 10' after the last key is pressed. If you
want to cancel the password timer, just go to page PW and hold down ^ and ˅ together for 2".
When the correct password is typed in a padlock is shown opening, while if the wrong password is given a flashing padlock appears.
input (NO)
input (NC)
input (NO)
Table 15 Disabling system restore and fault
Factory configurations of the outputs
Output
OUT 1
OUT 2
Table 16 Factory configurations of the outputs
Configuration of the functions associated with the outputs
OUT1
Activation condition
No associated function
No associated function
Presence of blocking
blocking errors the
errors
Presence of blocking
blocking errors the
errors
Table 17 Factory configurations of the outputs
ENGLISH
Present
Motor disabled + fault reset
Absent
Motor disabled + fault reset
Present
Absent
Present
2 (fault NO closes)
2 (Pump running NO closes)
Output contact
Activation condition
status
Contact always
No associated function
open
Contact always
No associated function
closed
In the case of
Output activation in
case of blocking errors
contact closes
In the case of
Output activation in
case of blocking errors
contact opens
66
Motor enabled
Motor enabled
Fault reset
Value
OUT2
Output contact status
Contact always open
Contact always closed
When the motor is
running the contact
When the motor is
running the contact
F3
F3
None
None
None
closes
opens