Herunterladen Inhalt Inhalt Diese Seite drucken

Factory Settings; Types Of Alarm; Alarm Description; Error Condition And Reset - DAB Evoplus small Installationsanweisung Und Wartung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 55
GB
ENGLISH

11. FACTORY SETTINGS

Parameter
Regulating mode
Twin operating mode
Pump start control

12. TYPES OF ALARM

Alarm Code
Alarm Symbol
e0 - e16; e21
e17 - e19
e20
e22 - e31
e32 - e35
e37
e38
e39 - e40
e46
e42
e56
e57
e58
13
Value
= Proportional differential pressure
 
regulation
= Alternate every 24h
 
ON
Table 1: Factory settings

Alarm Description

 
Internal Error
 
Short Circuit
Voltage Error
 
 
Internal Error
Electronic system excess temperature
 
Low voltage
 
High voltage
 
Pump blocked
 
 
Pump Disconnected
Dry operation
 
Motor excess temperature (motor
 
protector trips)
Frequency of PWM external signal less
 
than 100 Hz
Frequency of PWM external signal
 
greater than 5 kHz
Table 2: List of alarms
INFORMATION
Frequently asked questions (faq) on the ecodesign directive 2009/125/ec establishing a
framework for the setting of ecodesign requirements for energy-related products and its
implementing regulations:
http://ec.europa.eu/enterprise/policies/sustainable-business/documents/eco-de-
sign/guidance/files/20110429_faq_en.pdf
Guidelines accompanying commission regulations implementing the ecodesign directive:
http://ec.europa.eu/energy/efficiency/ecodesign/legislation_en.htm - see "circula-
tors.

13. ERROR CONDITION AND RESET

Display
Description
indication
 
e0 – e16
Internal error
Low mains
e37
 
voltage (LP)
High mains
e38
 
voltage (HP)
Critical over-
e32-e35
 
heating of
electronic parts
Reset
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- If the error persists, change the circu-
lator.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off.
- Check that the system ventilation ducts
are not blocked and that the environ-
ment temperature of the premises is
correct.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis