Modbus
58.1 modbus-tcp
58.1
modbus-tcp
Configure Modbus TCP/IP server settings.
58.1.1

modbus-tcp operation

Enable or disable the Modbus TCP/IP server.
Mode: Global Config Mode
Privilege Level: Operator
Format: modbus-tcp operation
no modbus-tcp operation
Disable the option
Mode: Global Config Mode
Privilege Level: Operator
Format: no modbus-tcp operation
58.1.2

modbus-tcp write-access

Enable or disable the write-access on Modbus TCP/IP registers. - Possible security risk, as Modbus
TCP/IP communication is not authenticated - .
Mode: Global Config Mode
Privilege Level: Operator
Format: modbus-tcp write-access
no modbus-tcp write-access
Disable the option
Mode: Global Config Mode
Privilege Level: Operator
Format: no modbus-tcp write-access