Herunterladen Inhalt Inhalt Diese Seite drucken

Ring-Coupling Enable; Ring-Coupling Disable - Hirschmann Automation GRS1040 Bedienungsanleitung - Referenz-Handbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Ring Coupling
49.1 ring-coupling
Paramete
Value
r
normal
P-6
extended
49.1.4

ring-coupling enable

Enable the Ring/Network coupling configuration with the coupling-port index.
Mode: Global Config Mode
Privilege Level: Operator
Format: ring-coupling enable <P-1>
Paramete
Value
r
slot no./port no.
P-1
49.1.5

ring-coupling disable

Disable the Ring/Network coupling configuration with the coupling-port index.
Mode: Global Config Mode
Privilege Level: Operator
Format: ring-coupling disable <P-1>
Paramete
Value
r
slot no./port no.
P-1
470
Meaning
Select the ring coupling mode for normal redundancy mode. The
slave does not respond to a failure in the remote ring or
network.
Select the ring coupling mode for extended redundancy mode The
slave responds to a failure in the remote ring or network.
Meaning
Meaning
RM CLI HiOS-3A-MR GRS1040
Release 6.1 09/2016

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis