Technical Data
Various measures can be taken to afford protection against
condensation:
1. Temperature control is recommended for this purpose (see Fig.
2. Physical dehumidifying. This is only effective in closed rooms. It
3. A humidity alarm can be installed to give a warning when
11-18
11-3). The water temperature is controlled as a function of room
temperature. This method is certainly to be preferred where there
are high room temperatures, low water temperatures and high
humidities.
comprises operating an air/water heat exchanger with cold water to
constantly condense the moisture out of the room air.
condensation is imminent. Such an alarm is available from
ENDRICH (www.endrich.com); when the temperature falls to within
2 K of dew point, a signal contact closes.
Operating Instructions
05.2006
6SE7087-6JK50