Connecting-up
7.3

Control connections

Standard
In the basic version, the unit has the following control connections on
connections
the CUMC control board:
♦ Serial interface (RS232 / RS485) for PC or OP1S (interface 1)
♦ One serial interface (USS bus, RS485) (interface 2)
♦ One control terminal strip with digital and analog inputs and outputs.
WARNING
Before the control cables and encoder cables are connected or
disconnected, the unit must be disconnected from the supply (24 V
electronic power supply and DC link/line voltage)!
If this measure is not observed, this can result in defects on the
encoder. A defective encoder can cause uncontrolled axis movements.
WARNING
The external 24 V infeed and all circuits connected to the control
terminals must meet the requirements for safety separation as
stipulated in EN 50178 (PELV circuit = Protective Extra Low Voltage).
NOTE
The earth of the control connections is connected inside the unit to the
PE conductor (earth) (PELV current circuit).
Fig. 7-4
7-10
X108
S1
X101
X103
S2
View of the CUMC
6SE7087-6JK50
Operating Instructions
SIMOVERT MASTERDRIVES
05.2006
Siemens AG