When first switched on, a discrepancy
in water level status is detected in float
A or between floats A and B.
W0-012
Float/probe connected to inlet B detect
a discrepancy in water level status than
Float/probe connected to inlet C
W0-013
ENGLISH
2. When controlled by depth sensor, use levels that are more separated from
each other.
1. Check that the float connected to inlet B is not stuck in the high position
(Drainage) or low position (Filling), and that the float connected to inlet A
is not stuck in the low position (Drainage) or high position (Filling).
In the case of level probes, check that no non-conductive substances (e.g.
plastic, wood, glass and paper) have been deposited on the probe
connected to inlet A and that the probe connection cable is intact.
2. In case of subsequent addition of the float/probe connected to inlet A,
carried out with the panel switched on, restart the panel.
Check that the float connected to inlet B is not stuck in the low position
(Drainage) or high position (Filling) and that the float connected to inlet C is
not stuck in the high position (Drainage) or low position (Filling).
In the case of level probes, check that no non-conductive substances (e.g.
plastic, wood, glass and paper) have been deposited on the probe connected
to inlet B and that the probe connection cable is intact.
68