Herunterladen Diese Seite drucken

DAB NGPANEL Installations- Und Wartungsanleitungen Seite 73

Vorschau ausblenden Andere Handbücher für NGPANEL:

Werbung

Holding
0006
Operating mode
Holding
0007
Absorbed current
Holding
0008
Type of control
0009
Holding
Tank with protection float
1001
Input
Panel Status
Input
1002
Panel Error* (H)
Input
1003
Panel Error* (L)
1004
Input
Pump 1 status
1005
Input
Pump 1* Error (H)
Input
1006
Pump 1* Error (L)
Input
1007
Pump 2 status
Input
1008
Pump 2* Error (H)
Input
1009
System status
Input
1010
Input
1011
Present Current Pump 1
1012
Input
Present Current Pump 2
Input
1013
Present Power Pump 1
Input
1014
Present Power Pump 2
Estimated water volume
2001
Input
(H)
Estimated water volume
2002
(L)
2003
Input
Panel operating hours (H)
2004
Input
Panel operating hours (L)
Number of pump 1 starts
Input
2005
(H)
Number of pump 1 starts
2006
Input
(L)
Number of pump 2 starts
Input
2007
(H)
Number of pump 2 starts
Input
2008
(L)
Number of pump 1 starts
input
2009
(partial) (H)
Number of pump 1 starts
Input
2010
(partial) (L)
Number of pump 2 starts
2011
Input
(partial) (H)
Number of pump 2 starts
Input
2012
(partial) (L)
Hours worked by pump 1
2013
Input
(H)
ENGLISH
2 → Enabled with activation every 2 days
0 → Drainage
R
0-1
1 → Filling
R
5-290
In tenths of A
0 → Float
R
0-2
1 → Level probe
2 → Depth sensor (analogue input)
0 → No float
R
0-3
1 →High float
R
0 -> Initial status
0-4
1 -> Standby status
2 -> Fault status
R
See Error list
R
See Error list
R
0 → Initial status
1 → Standby status (motor
stopped, no error)
0-6
2 → Motor running status
3 → Warning status
R
See Error list
R
See Error list
R
0 → Initial status
1 → Standby status (motor
stopped, no error)
0-6
2 → Motor running status
3 → Warning status
R
See Error list
R
See Error list
R
0 -> Initial status
0-4
1 -> Standby status
2 -> Fault status
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
63
2 →Low float
3 → Both floats
3 -> Warning status
4 -> Communication error
with MB
4 → Motor stopped due to
an error
5 → Pump excluded by
control
6 → Communication error
with MB
4 → Motor stopped due to
an error
5 → Pump excluded by
control
6 → Communication error
with MB
3 -> Warning status
4 -> Communication error
with MB

Werbung

loading