Fig. 13
NOTICE
▶ Make sure all the connections in the piping system are properly
sealed to prevent water leakages.
Installation requirements for water drainage piping
▶ Tilt the water drainage pipe downwards. The downslope piping must
be set (with a downward inclination of more than 1/100) for
drainage piping so that the condensate can flow easily.
▶ When connecting to a long water drainage pipe, the pipe must be
covered with insulation casing. Make sure the long pipe does not
become loose.
Air Flux – 6721876663 (2023/12)
<50mm
Fig. 14
[1]
Downslope piping
[2]
PVC adhesives
[3]
Drain pipe
[4]
PVC pipe (Ø 15mm) or rigid PVC pipe (VP-16)
0010053485-001
Fig. 15
[1]
Protection piping
[2]
Wall
[3]
Water drainage pipe
[4]
Extended water drainage pipe
6.4.2
Binding the pipes
1. Bind in the following sequence: power cord at the top, connecting
pipe in the middle, and drainage pipe at the bottom.
2. Confirm where the water outlet is before you connect the water
drainage pipe.
3. Do not pull hard on the snake tube during the binding process.
4. Cover the insulation materials if the pipes are pulled out horizontally.
5. Avoid the connection joints during binding in preparation for leakage
checks.
6. When the water drainage pipe is not long enough, and there is a need
to extend the water drainage pipe, make sure that protection casing
is used to wrap the pipe. Make sure that the water piping is not coiled
anywhere.
1
2
1
3
Installation
3
4
0010053484-001
2
4
0010022752-001
43