16.5
Configuration warnings
Installation and operating instructions • Wilo-SiFresh • Ed.02/2023-08
Code
Fault
574
Communication to CIF
module interrupted.
Additional information about causes and remedy:
The CIF module is connected to the pump in the terminal room via four contacts.
575
Remote control not pos-
sible by radio.
Additional information about causes and remedy:
System function not impaired.
If a software update does not eliminate the issue, contact Service.
576
Communication with Wilo
sensor interrupted.
Additional information about causes and remedy:
The system function is slightly impaired.
The system can no longer determine the internal fluid temperature.
577
Software update can-
celled.
Additional information about causes and remedy:
Software update was not carried out; system continues to operate with previous
software version.
578
Display and operating
unit defective.
Additional information about causes and remedy:
The display and operating unit is available as a spare part.
579
Software for display and
operating unit incompat-
ible.
Additional information about causes and remedy:
System function not impaired.
If a software update does not eliminate the issue, contact Service.
583
Fluid temperature too
high.
Additional information about causes and remedy:
High fluid temperatures lead to significant damage to the pump.
Table 28: Warning messages
Configuration warnings occur if an incomplete or contradictory configuration has been
made.
Code
Fault
601
Setpoint source not suit-
ably configured.
The setpoint source is not correctly configured. In the context menu there is a
link for configuring the setpoint source.
602
Setpoint source not
available.
The setpoint source or the CIF module is not correctly configured. In the context
menu there are links for configuration.
Cause
Remedy
Internal communica-
Check/clean contacts
tion to the CIF module
between CIF module and
interrupted.
electronic module.
The Bluetooth radio
Software update is recom-
module is faulty.
mended.
Contact Service.
Internal communica-
Check sensor cable, sensor
tion with Wilo sensor
socket and Wilo-Connector.
interrupted.
The software update
Software update with new
was not completed.
software bundle is recom-
mended.
A fault in the display
Replace display and operat-
and operating unit has
ing unit.
been identified.
Display and operating
Software update is recom-
unit cannot commu-
mended.
nicate correctly with
the system.
Fluid temperature is
Reduce fluid temperature.
hotter than 110 °C.
Cause
Remedy
Setpoint is not con-
Configure source or
nected to correct
select another source.
source. Input not suit-
ably configured.
Setpoint not connec-
Insert CIF module.
ted to existing CIF
Activate CIF module.
module.
en
105