Instruction manual FM-IM / FMX-IM
7.1.2
Quick-Teach-Procedure for devices with switching output
(FM(X)-IM-3UP63X, FM(X)-IM-3UR38X)
(menu structure Figure A, see inside front cover)
The Quick-Teach-Procedure is a simple switchpoint setting of the flow rate
with out teaching of the display range (MAX/MIN trim). For this purpose the
device is in display mode (Flow Display).
➤ Set the flow rate to the desired value.
➤
➤ Push the "Enter" button one time.
➤
DeltaFlow-Monitoring (∆ Flow Monitoring) (see Chapter 3.5.2 on p. 14)
➥
➤
starts.
➥
➤
If the entire LED-band is blinking green instead of yellow, the operation
can be continued.
➤ Push the "Enter" button for 5 s (equals 5 × blinking).
➤
LED 5 on the band display changes from green to yellow; the rest of the LEDs
on the band display are synchronously blinking green. After 5 s (equals 5 ×
blinking), the green LEDs on the band display extinguish; LED 5 continues
to blink in the same rhythm. The actual flow rate of the monitored system is
taught as Teach-Value.
➤ Push in increments the "Set" button or push in increments the "Mode"
➤
button (Set SP Flow).
Pushing the "Set" button increases the switchpoint in increments.
Pushing the "Mode" button decreases the switchpoint in increments.
➤ Push the "Enter" button one time.
➤
The switchpoint is stored.
➥
➤
The entire LED-band will be green for 1 s, afterward the switchpoint is
stored and the device switches to the display mode (Flow Display).
32
Hans Turck GmbH & Co. KG • Tel. +49 (0) 208/4952-0 • Fax +49 (0) 208/4952-264