 ,QVWDOOLQJ WKH UHIULJHUDQW SLSLQJ
A Front piping cover
B Piping cover
C Stop valve
D Service panel
E Bend radius : 100 mm - 150 mm
)LJ 
A 6WRS YDOYH /LTXLG VLGH!
B 6WRS YDOYH *DV VLGH!
C Service port
D Open/Close section
E Local pipe
)LJ 
(1) 1
)LJ 
(2) 1
)LJ 

F Sealed, same way for gas side
G Pipe cover
H Do not use a wrench here.
Refrigerant leakage may result.
I Use two wrenches here.
2
2
 5HIULJHUDQW SLSLQJ )LJ 
Remove the service panel D (three screws) and the front piping cover A (two screws)
and rear piping cover B (two screws).
1 Perform refrigerant piping connections for the indoor/outdoor unit when the outdoor
unit's stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping.
3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)
4 Vacuumize the refrigerant lines through the service port of the liquid and gas stop
valves. And then open the stop valves completely (for both the liquid and gas stop
valves). This will completely connect the refrigerant lines of the indoor and outdoor
units.
‡ ,I WKH VWRS YDOYHV DUH OHIW FORVHG DQG WKH XQLW LV RSHUDWHG WKH FRPSUHVVRU DQG
control valves will be damaged.
‡ 8VH D OHDN GHWHFWRU RU VRDS\ ZDWHU WR FKHFN IRU JDV OHDNV DW WKH SLSH FRQQHF-
tion sections of the outdoor unit.
‡ 'R QRW XVH WKH UHIULJHUDQW IURP WKH XQLW WR SXUJH DLU IURP WKH UHIULJHUDQW
lines.
‡ $IWHU WKH YDOYH ZRUN LV FRPSOHWHG WLJKWHQ WKH YDOYH FDSV WR WKH FRUUHFW WRUTXH
 WR  1 P  WR  NJI FP 
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.
5 Use sealant to seal the ends of the thermal insulation around the pipe connection
sections to prevent water from entering the thermal insulation.
 5HIULJHUDQW SLSH DLUWLJKW WHVWLQJ PHWKRG
(1) Connect the testing tools.
‡ 0DNH VXUH WKH VWRS YDOYHV A B are closed and do not open them.
‡ $GG SUHVVXUH WR WKH UHIULJHUDQW OLQHV WKURXJK WKH VHUYLFH SRUW C of the liquid
stop valve A and the gas stop valve B.
 'R QRW DGG SUHVVXUH WR WKH VSHFL¿HG SUHVVXUH DOO DW RQFH DGG SUHVVXUH OLWWOH E\ OLW-
tle.
1 Pressurize to 0.5 MPa (5 kgf/cm
pressure does not decrease.
2 Pressurize to 1.5 MPa (15 kgf/cm
pressure does not decrease.
3 Pressurize to 4.15 MPa (41.5 kgf/cm
perature and refrigerant pressure.
 ,I WKH VSHFL¿HG SUHVVXUH KROGV IRU DERXW RQH GD\ DQG GRHV QRW GHFUHDVH WKH SLSHV
have passed the test and there are no leaks.
‡ ,I WKH VXUURXQGLQJ WHPSHUDWXUH FKDQJHV E\ ƒ& WKH SUHVVXUH ZLOO FKDQJH E\
about 0.01 MPa (0.1 kgf/cm
2
G). Make the necessary corrections.
(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source
of the gas leak.
 6WRS YDOYH RSHQLQJ PHWKRG
(1) Gas side (Fig. 4-6)
1 Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-
wise direction to open.
2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position.
(2) Liquid side (Fig. 4-7)
1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.
(ø6.35: Approximately 4.5 revolutions) (ø9.52: Approximately 10 revolutions)
2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position.
A Valve
B Unit side
C Handle
D Cap
E Local pipe side
Refrigerant pipes are protectively wrapped
‡ 7KH SLSHV FDQ EH SURWHFWLYHO\ ZUDSSHG XS WR D GLDPHWHU RI ¡ EHIRUH RU DIWHU FRQ-
necting the pipes. Cut out the knockout in the pipe cover following the groove and
wrap the pipes.
Pipe inlet gap
‡ 8VH SXWW\ RU VHDODQW WR VHDO WKH SLSH LQOHW DURXQG WKH SLSHV VR WKDW QR JDSV UH-
main.
(If the gaps are not closed, noise may be emitted or water and dust will enter the
unit and breakdown may result.)
2
*  ZDLW ¿YH PLQXWHV DQG PDNH VXUH WKH
2
*  ZDLW ¿YH PLQXWHV DQG PDNH VXUH WKH
2
G) and measure the surrounding tem-
F Open position side
G Service port
H :UHQFK KROH
I 5HIULJHUDQW ÀRZ GLUHFWLRQ