Number / Fault
Cause
F110
During test pulse measurement, the current
has increased significantly faster than was
Mld di/dt
expected. Thus for the 1st test pulse, an
overcurrent condition occurred within the first
half of the minimum switch-on time
F111
A fault has occurred while calculating the
equalization function.
Fault e_Func
F112
The individual leakage test results deviate too
significantly.
Unsym I_sigma
F114
The converter has automatically stopped the
automatic measurement due to the time limit
MId OFF
up to power-up having been exceeded or due
to an OFF command during the measurement,
and has reset the function selection in P115.
F115
A fault has occurred during calculations in the
context of the MotID.
KF internal
F116
See TB documentation
Technology board fault
F117
See TB documentation
Technology board fault
F118
See TB documentation
Technology board fault
F119
See TB documentation
Technology board fault
F120
See TB documentation
Technology board fault
F121
See TB documentation
Technology board fault
F122
See TB documentation
Technology board fault
F123
See TB documentation
Technology board fault
F124
See TB documentation
Technology board fault
F125
See TB documentation
Technology board fault
F126
See TB documentation
Technology board fault
F127
See TB documentation
Technology board fault
F128
See TB documentation
Technology board fault
F129
See TB documentation
Technology board fault
Siemens AG
6SE7087-6KP60
SIMOVERT MASTERDRIVES
Operating Instructions
Counter-measure
- There may be a short-circuit between two
converter outputs.
- The motor rating plate data have not been
correctly parameterized.
- The motor leakage is too low.
Re-start with P115 function selection = 2
"Motor identification at standstill". The ON
command must be given within 20 sec. after
the alarm message A078 = standstill
measurement has appeared.
Cancel the OFF command and re-start
measurement.
Power-down the converter and electronics and
power-up again.
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
Faults and Alarms