06.2005
Switch settings
Siemens AG
6SE7087-6KP60
SIMOVERT MASTERDRIVES
Switch
Meaning
S3 (4,5,6)
AI2: Switching between current/voltage input
•
•
Jumper 5,6
Voltage input
•
•
Jumper 4,5
Current input
S4 (1,2,3)
AO2: Switching between current/voltage output
•
•
Jumper 1,2
Voltage output
•
•
Jumper 2,3
Current output
To set switches S3 and S4 on units with a width of up to 90 mm, the
side wall has to be removed; on units with a width of more than 90 mm,
the front cover has to be removed. See Chapter 5.2 "Installing the
optional boards".
CU
S3
S4
Fig. 7-6
Setting of switches S3 and S4
Operating Instructions
(default setting)
(default setting)
PBI
6
4
3
1
Connecting-up
7-11