Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens simovert masterdrives Betriebsanleitung Seite 252

(dc-ac) bauform kompakt plus
Vorschau ausblenden Andere Handbücher für simovert masterdrives:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical Data
Derating curves
12-6
Permissible rated input voltage in %
according to VDE 0110 / IEC 664-1
(not required by UL / CSA)
100
75
50
0
1000
Height above sea level in m
Permissible rated current in %
100
90
80
70
60
0
1000
Height above sea level in m
Permissible rated current in %
100
75
50
25
0
0
10
20
Coolant temperature in °C
Permissible rated current in %
100
75
50
0
2
4
6
8
10
Fig. 12-1
Derating curves
2000
3000
4000
2000
3000
4000
30
40
50
16 18
12
14
Pulse frequency
Operating Instructions
06.2005
Height
Derating
[m]
factor K
1
1000
1.0
2000
0.9
3000
0.845
4000
0.8
Temp
Derating
[°C]
factor K
2
50
0.80
45
1.0
40
1.125
35
1.25 *
30
1.375 *
25
1.5 *
*See note
below
Pulse
Derating
frequency
factor K
3
kHz
6
1.0
8
0.9
10
0.8
12
0.7
14
0.6
16
0.5
6SE7087-6KP60
Siemens AG
SIMOVERT MASTERDRIVES

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Kompakt plus

Inhaltsverzeichnis