Faults and Alarms
Number / Fault
Cause
F008
The lower limit value of 76 % of the DC link
voltage (P071 Line Volts), or of 61 % when
DC link undervoltage
kinetic buffering has been enabled, has been
fallen short of.
Undervoltage in the DC link in 'normal'
operation (i.e. no SIMULATION).
Undervoltage in the DC link with active kinetic
buffering and speed less than 10 % of the
rated motor speed.
It was a 'brief power failure' which was not
detected until system recovery (auto restart
flag).
F010
Due to excessive DC link voltage, shutdown
has taken place:
DC link overvoltage
Line voltage
380 V - 480 V
Note:
Only at U800 = 1 and f(Pulse) > f(derating)
Lower threshold value than F006 !
F011
Overcurrent shutdown has occurred.
The shutdown threshold has been exceeded.
Overcurrent
F012
During excitation of the induction motor, the
current did not rise above 12.5 % of the
I too low
setpoint magnetizing current for no-load
operation.
F014
During excitation of the motor, the current
component is less than 25 % of the motor no-
I too low
load current.
Note:
Only for U800 = 1
Irrespective of the type of control
(Difference to F012)
13-2
DC link range Shutdown
value
510 V - 650 V
740 V
Operating Instructions
Counter-measure
Check
- Input DC voltage
- DC link
Check the supply voltage
Check the braking resistor
Converter operates regeneratively without a
feedback possibility. Braking unit must be set
to the lower response threshold (673 V)
- Check the converter output for short-circuit or
earth fault
- Check the load for an overload condition
- Check whether motor and converter are
correctly matched
- Check whether the dynamic requirements
are too high
Only for closed loop n/f/T control (P100 = 3, 4
or 5)
If no motor is connected, go into the simulation
mode P372.
Check current detection, check power section.
Check the output contactor
Check the motor cable
6SE7087-6KP60
SIMOVERT MASTERDRIVES
02.2005
Siemens AG