Total failure of the
If the display fails to come on some time after sunrise:
display
-
-
*

Status codes

Service class 1
Status codes of these class only arise momentarily and are caused by the public grid.
The initial response of the inverter in this case is to disconnect itself from the grid. The grid
is subsequently checked for the stipulated monitoring period. If no further problem has
been detected by the end of this period, then the inverter will resume feeding energy into
the grid.
Code
Description
102
Grid voltage above permit-
ted limit
103
Grid voltage below permit-
ted limit
105
Mains frequency above
permitted limit
106
Mains frequency below per-
mitted limit
106
Check the AC voltage ON the inverter connections:
the AC voltage must be 230 V (+ 10 % / - 5 %)*
Carrying out an AC reset: Disconnect the inverter when not under load from the AC
supply and switch it back on
The mains voltage tolerance depends on the country setup
Behaviour
1. Mains voltage error
2. Incorrect values in the Ser-
vice Menu / Wrong Setup
3. Measuring error on the filter
board
1. Mains voltage error
2. Wrong AC cabling
3. Incorrect values in the Ser-
vice Menu / Wrong Setup
4. Bad contact: wall bracket <-
> filter board
5. Measuring error on the filter
board
1. Mains voltage error
2. Incorrect values in the Ser-
vice Menu / Wrong Setup
3. Reconnection limit
4. Ripple control signals
5. Measuring error on the filter
board
1. Mains voltage error
2. Incorrect values in the Ser-
vice Menu / Wrong Setup
3. Ripple control signals
4. Measuring error on the filter
board
Remedy
1. Check mains voltage
2. Check values in the Service
Menu / Check Setup
3. Change filter board
1. Check mains voltage
2. Check AC cabling
3. Check values in the Service
Menu / Check Setup
4. Check AC wall bracket
screws
5. Change filter board
1. Check mains voltage
2. Check values in the Service
Menu / Check Setup
3. Normal legal requirement,
no error (50,05Hz)
4. Report to TSI specialist
5. Change filter board
1. Check mains voltage
2. Check values in the Service
Menu / Check Setup
3. Report to TSI specialist
4. Change filter board