Herunterladen Inhalt Inhalt Diese Seite drucken

Fronius Symo 10.0-3-M Serviceanleitung, Ersatzteilliste Seite 109

Netzgekoppelter wechselrichterfronius
Vorschau ausblenden Andere Handbücher für Fronius Symo 10.0-3-M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
309
Too high DC1 voltage
313
Too high DC2 voltage
Service class 4
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.
Code
Description
401
Communication error be-
tween Recerbo and power
stage set
406
Temperature sensor in DC
semiconductor module de-
fective
407
Temperature sensor on the
power stage set
408
On the inverter an unac-
ceptably high DC injection
was detected
412
Adjusted fix voltage beyond
the accessible MPP range
415
Wire shutdown tripped
416 - 425
Communication error be-
tween power stage set and
Recerbo
Behaviour
1. PV generator voltage too
high in MPP1
2. Wrong DC cabling in MPP 1
3. Measuring error on the pow-
er stage set
1. PV generator voltage too
high in MPP 2
2. Wrong DC cabling in MPP 2
3. Measuring error on the pow-
er stage set
Behaviour
1. Ribbon cable between pow-
er stage set and filter board
faulty or not connected proper-
ly
2. Ribbon cable defective
3. Recerbo not plugged in cor-
rectly
4. Recerbo defective
5. Power stage set defective
6. Filter board defective
1. Defective temperature sen-
sor in semiconductor module
2. Defective circuit on the pow-
er stage set
1. Defective temperature sen-
sor on the power stage set
2. Defective circuit on the pow-
er stage set
1. Asynchronous AC grid
2. Power stage set defective
1. Fix voltage was adjustable
too high or too low
1. Option card tripped a wired
shutdown
1. Occurs once - PSP commu-
nication error
2. Unknown option card blocks
the inverter
3. Ribbon cable between filter
and power stage set defective
4. Recerbo defective
5. Filter board defective
6. Power stage set defective
Remedy
1. Check PV configuration
2. Check DC cabling
3. Change DC board. After-
wards if necessary AC board
1. Check PV configuration
2. Check DC cabling
3. Change DC board. After-
wards if necessary AC board
Remedy
1. Check ribbon cable between
Recerbo and power stage set
2. Change ribbon cable
3. Check Recerbo plug
4. Change Recerbo
5. Change AC board
6. Change filter board
1. Change DC board
2. Change DC board
1. Change AC board
2. Change AC board
1. Check AC grid
2. Change AC board
1. Check adjustments in the
service menu
1. Automatically corrected, op-
tion card stopped the inverter
1. Automatically corrected
2. Software update
3. Change ribbon cable
4. Change Recerbo
5. Change filter board
6. Change AC board
109

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis