Herunterladen Inhalt Inhalt Diese Seite drucken

Fronius Symo 10.0-3-M Serviceanleitung, Ersatzteilliste Seite 111

Netzgekoppelter wechselrichterfronius
Vorschau ausblenden Andere Handbücher für Fronius Symo 10.0-3-M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
447
Isolation failure detected
448
Neutral wire fault
451
Flash of the guard defective
452
Communication between
filter & power stage set
faulty
453
Processor guard detected a
faulty grid voltage
454
Processor guard detected a
faulty grid frequency
456
Error in the Anti Islanding
monitoring detected
457
Grid relais do not release
458
RCMU selftest failed
Behaviour
1. PV generator grounded
2. PV generator grounding er-
ror
3. Measuring circuit on power
stack defect
1. No neutral wire detected
2. Wrong setup
3. Bad contact: wall bracket <-
> inverter
4. Filter board defective
1. Grid problem
2. Defective AC guard on filter
board
3. Defective AC guard on pow-
er stage set
1. Communication problem
caused by temporary environ-
mental disturbances (grid,
EMC, ...)
2. Ribbon cable between filter
board and power stage set de-
fective
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Measuring error
2. Grid problem
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Measuring error
2. Grid problem
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Occurs once
2. Software problem
3. Measuring on filter board
4. Measuring circuit for Anti Is-
landing defective
1. Occurs once
2. Grid test time is too low
3. Relay got stuck
1. RCMU measurement defect
Remedy
1. Use only ungrounded mod-
ules
2. Check PV generator
3. Change DC board. After-
wards if necessary AC board
1. Check wiring
2. Check country setup
3. Check AC wall bracket
screws
4. Change filter board
1. Automatically corrected
2. Change filter board
3. Change AC board
1. Automatically corrected
2. Change ribbon cable
3. Change filter board
4. Change AC board
1. Software update
2. Automatically corrected
3. Change filter board
4. Change AC board
1. Software update
2. Automatically corrected
3. Change filter board
4. Change AC board
1. Restart inverter
2. Software update
3. Change filter board
4. Change AC board
1. Restart inverter
2. Change settings
3. Change AC board
1. Change filter board
111

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis