Herunterladen Inhalt Inhalt Diese Seite drucken

Fronius Symo 10.0-3-M Serviceanleitung, Ersatzteilliste Seite 118

Netzgekoppelter wechselrichterfronius
Vorschau ausblenden Andere Handbücher für Fronius Symo 10.0-3-M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
767*
Power limitation not reada-
ble
768
Power limitation while feed-
ing-in operation changed
772
Memory on the storage
print not available, due to
safety reasons the inverter
does not feed in
773
Memory on the storage
print not initialised, due to
safety reasons the inverter
does not feed in
775
Faulty programming of the
power stage set
782* - 783*
Error during update
784*
Waiting on flash / busy
789*
Setup CRC failed
794*
Flash data structure defect
901
Deviation of measurement
channel 1
902
Deviation of measurement
channel 2
903
Deviation of measurement
channel 3
904
Deviation of measurement
channel 4
905
Deviation of measurement
channel 5
990
Deviation of output from ra-
diation sensor value too big
991
Deviation of radiation sen-
sor too big
992
No radiation sensor values
or value(s) not permitted
993
Faulty energy report
118
Behaviour
1. Occurs once
2. Recerbo defective
1. Attached storage print is be-
ing connected or disconnected
during feeding in operation
1. SSP not connected
1. Memory not programmed or
memory lost
2. Defective Recerbo
1. Power stage set or filter
board not programmed
1. Occurs once
2. Recerbo defective
1. Occurs once
2. Recerbo defective
1. Wrong / defective data in
flash
2. Recerbo defective
1. Wrong / defective data in
flash
2. Recerbo defective
Current of channel 1 deviates
from the other channels
Current of channel 2 deviates
from the other channels
Current of channel 3 deviates
from the other channels
Current of channel 4 deviates
from the other channels
Current of channel 5 deviates
from the other channels
Difference between the perfor-
mance of the irradiation sensor
and that of the inverter too big
The radiation sensor deviates
too far
The radiation sensor does not
return any values or returns
values that are not permitted
Faulty energy report due to
missing archive values
Remedy
1. Automatically corrected
2. Change Recerbo
1. Automatically corrected
1. Check SSP
1. Reload setup
2. Change Recerbo
1. See device -> info menu:
look for missing versions infos
and change defective print
1. Automatically corrected
2. Change Recerbo
1. Automatically corrected
2. Change Recerbo
1. Update software
2. Change Recerbo
1. Update software
2. Change Recerbo
Check settings, DC fuse and
modules
Check settings, DC fuse and
modules
Check settings, DC fuse and
modules
Check settings, DC fuse and
modules
Check settings, DC fuse and
modules
Check archives values, shad-
ow of the modules, blown
string fuse or defect
Check if your radiation sensor
is soiled, shaded or defect
Check the cable lines of the ra-
diation sensor
Check archive values at Froni-
us Solar.web server or Data-
logger

Quicklinks ausblenden:

Werbung