Visual inspections

General

The following must be visually inspected without any further dismantling of the device. Ob-
vious defects in any safety-related device components are unacceptable. Defects that
could pose a risk during the visual inspection must also be recorded.
Any defects that could cause other hazards must be repaired immediately or restrictions
placed on the further use of the system until repairs have been effected.
Mains supply and
-
connecting lines
-
-
-
-
-
IMPORTANT!
IEC 60364-5-52 serves as the basis for determining the cross-section and current ca-
pacity of mains cables.
As the way the cables are laid and insulated, the ambient temperature and the current ca-
pacity can vary, the requirements set out in IEC 60364-5-52 are to be observed when
changing mains leads. Also refer to the applicable requirements and standards in your
country.
Housing and cov-
-
ers
-
-
-
-
-
Adjustment and
-
display devices
Rating plate and
-
warning stickers
-
Connecting lines and other cables must not be damaged or defective
Insulation must not be damaged (do not use insulating or adhesive tapes to repair
damage)
Connectors and plug connections must not be damaged or deformed
Strain-relief devices, bending-protection devices, line routings or mountings must all
be effective
Lines/plugs must be suitable for the application and the power level
Fuse cartridges and device fuse holders must not be faulty
All housing components, insulation components and protective covers must be pres-
ent and undamaged
No unauthorised modifications must have been made (e.g. installations, conversions
that have not been approved by the manufacturer)
Cooling openings must not be dirty or blocked and an air filter must be present
Any dirt, corrosion or degradation that impairs safety must not be visible
There must be no signs of overloading or improper use
There must not be any conductive objects in the housing
Control elements and indicators must not be faulty
Safety-related labels (e.g. warning notices, earthing symbols, rating plates, etc.) must
be present. Replace, update or correct the labels as required
The legibility of all safety-related labels or symbols, measurement data and positioning
indicators must be ensured