Configuration using INGECON SUN Manager
14. Configuration using INGECON SUN Manager
The INGECON SUN String Control unit must be configured using the INGECON SUN Manager software.
The most important settings parameters are:
•
Number of strings installed: the number of strings connected to your unit. The strings must be connected
to the lowest-numbered connectors (from left to right). The number of strings is 16 by default.
•
Rated current of each string: Insert in this field the nominal value of the current of each string in amps.
•
Average Percentage deviation: the percentage of deviation between the current of each string and the
average of the currents of the unit for which we want an alarm to trigger.
•
Time before alarm: the time that the string must provide a current above the percentage of average
deviation before the unit triggers an alarm. It is defined in seconds.