If the remote keyboard must be installed over 200 m away from the plan network, a power unit must be installed near the remote keyboard.
The remote keyboard cannot be installed more than 500 m away.
The only difference between this and a remote keyboard up to 200 metres is that the power unit must be to terminals 1 and 2 of the T shunt (the one near
the remote keyboard). In this case a 3-wire cable connecting the two T-shunts is sufficient.
If just one chiller is connected, the connection diagram is:
3x1 mm
2
Shielded and
twisted
Unit
Figure 9.18: diagram for connecting a remote keyboard from 200 m to 500 m.
Figure 9.19: wiring diagram for connecting a remote keyboard from 200 m to 500 m.
127
Installation, use and maintenance manual - Original instructions