Herunterladen Inhalt Inhalt Diese Seite drucken

Fuses And Leds Of The Controller; Possible Faults When Changing The Tank - Grundfos Oxiperm OCD-164 Montage- Und Betriebsanleitung

(30-2000 g/h)
Vorschau ausblenden Andere Handbücher für Oxiperm OCD-164:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 106

8.5 Fuses and LEDs of the controller

Fig. 24 Dosing controller
Pos. Description
Backup fuse, solenoid valve, system
SI 1
drain
Backup fuse, solenoid valve, H
SI 2
rinsing
Backup fuse, solenoid valve, bypass
SI 3
water
Backup fuse, NaClO
(NaClO
2
SI 4
dosing pump
SI 5
Backup fuse, HCl dosing pump
SI 6
Backup fuse, H
O dosing pump
2
Backup fuse, solenoid valve, enclosure
SI 7
exhaust
Backup fuse, solenoid valve, exhaust
SI 8
device, preliminary
SI 9
Internal supply voltage ± 15 V
SI 10 Main fuse of the system
SI 19 Internal supply voltage ± 12 V / +8 V
SI 12 Internal supply voltage +24 V
SI 13 Internal supply voltage +5 V
1
LED (green) - RUN
2
LED (red) - ERROR
3
LED (red) - battery
4
LED (yellow) - WATCHDOG
5
Battery
In the correct operating state, the LED (1) is green, and the LED
(4) is yellow. If there is a fault, e.g. if no more programs are
available or the memory card is defective, the LED (1) is green
and the LED (2) is red.
In this case:
Turn the controller off and on again. If the error still occurs:
Switch off the controller, remove the battery, switch the
controller on again. Wait for the program to be loaded from the
memory. Insert the battery again. If the error still occurs:
Reinstall the program, or change the memory card.
38
Ampere
1 A
O
2
1 A
1 A
/HCl)
2
6.3 A
6.3 A
6.3 A
1 A
1 A
100 mA
10 A
100 mA
2 A
1 A

8.6 Possible faults when changing the tank

Each of the suction lines has a pre-empty and an empty-signal
contact. If the level in the container reaches the "pre-empty
signal" contact, an alarm message appears on the display, yet the
system does not stop.
If the level reaches the "empty signal" contact, an alarm message
appears on the display, and the system shuts down.
Pre-empty signal
A ON ACK
Pre-empty signal
NaClO
2
23-04-10 14:36:12
The system remains in operation until the empty-signal contact is
activated.
Empty signal
A ON ACK
Empty signal
NaClO
2
23-04-10 14:36:12
The system switches off automatically.
Change of tank at "pre-empty" alarm
The "pre-empty" alarm appears on the display.
1. Remove the suction line from the tank.
2. The system switches off automatically, the "HCl or NaClO
empty" alarm is displayed.
3. Fit the suction line into the new tank.
4. Press the [F4] key to acknowledge the two alarm messages.
5. Press [Enter] to re-activate the system.
Change of tank at "empty" alarm
The "empty" alarm appears on the display.
1. Remove the suction line from the tank.
2. Fit the suction line into the new tank.
3. Press the [F4] key to acknowledge the two alarm messages.
4. Press [Enter] to re-activate the system.
Warning
Only use standard tanks.
Never pour the contents of the tank into another one!
There is a great danger of residual chemicals being
poured into the wrong tank.
The procedure is identical for both tanks: If both
tanks are changed, up to 4 alarm messages have to
Note
be acknowledged, before the system can be
re-activated.
1/1
1/1
2

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis