Herunterladen Inhalt Inhalt Diese Seite drucken

Alarm Unit; Option Of Connection To An External Alarm; Sump Tank; Pumped Fluids - SFA SANICUBIC 1 Bedienungs- & Installationsanleitung

Vorschau ausblenden Andere Handbücher für SANICUBIC 1:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 22
UK
3 .6 .1 Electrical characteristics
Table 3: Electrical characteristics of the control box
Parameter
Value
Nominal power
supply
1 ~ 220-240 V AC
Network frequency
50-60 Hz
Protection index
IPX4
3 .6 .2 Technical characteristics of the detection device
Analog level sensor:
• Input voltage 0 - 5 V
Process outputs:
• One potential-free signalling output (250 V, 16 A) NO Contact
• One signalling output for the wired alarm unit that comes with the device
(except SANICUBIC® 2 Pro): 12V
3 .6 .3 Dimensions of the remote control box

3 .7 Alarm unit

3 .7 .1 Technical characteristics of the alarm device
SANICUBIC® alarm unit:
SANICUBIC® 1; SANICUBIC® 1 WP; SANICUBIC® 1 VX; SANICUBIC® 2 Classic;
SANICUBIC® 2 VX:
Wired alarm unit
5m cable
Audio and visual information
Protection index: IP20
SANICUBIC® 2 Pro:
HF alarm unit 868 MHz (radio)
Unobstructed range: 100 m
Audio and visual information
Protection index: IP20
3 .7 .2 Dimensions of the remote alarm unit

3 .8 Option of connection to an external alarm

Option of externalising the alarm signal (depending on the model). Dry
contact (no voltage) NO (normally open) operated by a relay.
Alarm contact can be connected to a powered system.
This contact closes as soon as the station is in alarm mode (except in the case
of area alarm) and remains closed as long as the alarm sounds.
External alarm
Max. 250 V / 16A

3 .9 Sump tank

The sump tank is designed for pressure-free operation. Wastewater is collec-
ted there at atmospheric pressure before being discharged to the sewer. The
ventilation duct allows the tank to always remain at atmospheric pressure

3 .10 Pumped fluids

Pumping unauthorised fluids
Dangerous for people and the environment!
w Only discharge authorised pumped fluids in the public sewerage
network
Authorised pumped fluids:
The following liquids are allowed in discharge systems:
Water contaminated by domestic use, human excrement.
Unauthorised pumped fluids:
The following liquids and substances are banned:
• Solid materials, fibres, tar, sand, cement, ash, coarse paper, hand towels,
wipes, cardboard, rubble, rubbish, slaughterhouse waste, oils, greases,
etc.
• Wastewater containing harmful substances (for example, untreated
greasy waste from restaurants). Pumping these liquids and substances
requires the fitting of a compliant grease trap.
• Rain water.

3 .11 Noise level

The noise level depends on the fitting conditions and operating point. This
sound pressure level Lp is less than 70 dB (A).
4

INSTALLATION / FITTING

4 .1 Installing the pumping station

• The characteristics shown on the rating plate have been compared with
those on the order and installation (supply voltage, frequency).
• The installation room must be protected against frost.
• The installation room is adequately lit.
• The work has been prepared in accordance with the dimensions shown in
the example installation and standard EN 12056-4.
• The plant room where the SANICUBIC® will be installed must be large
enough to allow a 600 mm clearance around and above the device to faci-
litate maintenance.
• The alarm signal is always visible to the user (if necessary, use an external
alarm contact switch).
• In case of discharge of greasy effluents, the use of a degreasing tank is es-
sential.
Wastewater other than those mentioned above, for example, of artisanal or
industrial origin, must not be discharged into the pipes without prior treat-
ment.

4 .2 Electrical connection

Electrical connection work performed by an unqualified
individual .
Risk of death by electric shock!
w The electrical connection must be performed by a qualified
and licensed electrician.
w The electrical installation must meet the current standards in
the country
Wrong supply voltage .
Dry contact
Damage to the pumping station!
NO
w The supply voltage must not differ by more than 6% of the
rated voltage specified on the rating plate.
The power supply must be class 1. The device must be connected to an ear-
thed junction box. The electrical power supply must be protected with a high
sensitivity circuit breaker set to 10 Mini Amps for SANICUBIC 1/ SANICUBIC 1
WP, 20 Mini Amps for SANICUBIC 2 Classic/SANICUBIC 2 Pro/SANICUBIC 2 VX
single-phase and 25 Amps for SANICUBIC 2 VX three-phase. This connection
must be used exclusively for the SANICUBIC® power supply. If the cord of this
device is damaged, it must be replaced by the manufacturer or its after-sales
service in order to avoid any danger to users.
4 .3 Fitting the pumping station
Fit the pumping station on the bare ground and level it with a bubble level.
To avoid any risk of the pumping station floating, attach it to the ground
using the mounting kit provided.
17

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sanicubic 2 vx

Inhaltsverzeichnis